Leak checks limit refrigerant loss and help assess the condition of your system.
Understanding the CO₂ Equivalent Calculation
To comply with regulations concerning fluorinated greenhouse gases, or F-gases, it is essential to understand the concept of CO₂ equivalent [1]. This measurement provides a standardised way to express the environmental impact of different refrigerants. Instead of just measuring the weight of the gas, the CO₂ equivalent translates that weight into its corresponding global warming effect relative to carbon dioxide. This is the foundation upon which leak check obligations are built.
The calculation itself is a straightforward process based on two key figures: the total refrigerant charge of your system and the Global Warming Potential (GWP) of the specific gas it uses. The formula is as follows:
(Refrigerant Charge in kilograms x Global Warming Potential) / 1,000 = Tonnes of CO₂ equivalent
Let us break this down. First, you need the refrigerant charge, which is the total amount of refrigerant gas contained within the air conditioning or refrigeration system, measured in kilograms. Second, you need the GWP of that gas. The GWP is a scientifically determined value that indicates how much heat a greenhouse gas traps in the atmosphere over a specific time, compared to carbon dioxide. By multiplying these two figures, you determine the total warming impact in kilograms of CO₂ equivalent. The final step, dividing by 1,000, simply converts this figure into tonnes, which is the standard unit used for regulatory thresholds [1][2]. Performing this calculation accurately is the first and most critical step in determining your legal obligations for leak checking.
How to Find Your System's Information
To use the formula for CO₂ equivalent, you must first locate accurate information about your equipment. The two primary pieces of information you need are the type of refrigerant and the size of the charge in kilograms. Fortunately, this data is usually available directly on the equipment or within its service history.
The most common place to find this information is on the equipment label or data plate. This is typically a metal plate or a durable sticker affixed to the outer casing of the unit, often the outdoor condenser unit. This label contains essential technical specifications from the manufacturer, including:
- The model and serial number.
- Electrical specifications.
- The type of refrigerant the system was designed to use (for example, R410A or R32).
- The factory refrigerant charge in kilograms.
For systems that have been in operation for some time, the information on the original label might not be the complete story. This is where service records become invaluable. A professional service record or logbook, maintained by a qualified technician, documents all maintenance activities. If refrigerant has been added to or removed from the system during its operational life, these records should show the current total charge. This makes the service log a more reliable source for the actual, present day charge compared to the original factory specification. If you cannot locate either the equipment label or the service records, it is strongly advised to consult a certified refrigeration specialist. A professional can safely identify the gas and determine the charge, ensuring your calculations are based on correct information.
The Significance of Global Warming Potential (GWP)
The Global Warming Potential, or GWP, of a refrigerant is a measure of its potency as a greenhouse gas. A higher GWP value indicates a greater warming impact per kilogram compared to carbon dioxide, which has a GWP of 1 by definition. This value is a crucial factor in environmental regulations because it allows for a direct comparison of different gases and their potential contributions to climate change [1].
The regulations focus on the GWP of gases because a small leak of a high GWP refrigerant can have a disproportionately large environmental impact. Consider the two examples provided in the technical guidance:
| Refrigerant | Global Warming Potential (GWP) |
|---|---|
| R410A | 2088 |
| R32 | 675 |
As the table illustrates, the difference in impact can be substantial. A one kilogram leak of R410A has the same warming effect as a 2,088 kilogram leak of carbon dioxide [2]. In contrast, a one kilogram leak of R32 has the same effect as 675 kilograms of carbon dioxide [2]. This means that R410A is more than three times as potent a greenhouse gas as R32.
The core principle is to assess the potential environmental impact of a system, which is why the calculation of CO₂ equivalent, heavily reliant on GWP, is a cornerstone of current regulations [1].
Understanding this helps to explain why two systems of the same physical size might have very different maintenance requirements. A system with a small charge of a high GWP gas could easily exceed the CO₂ equivalent threshold for mandatory checks, while a much larger system using a low GWP refrigerant might not. It is the potential for environmental harm, not simply the volume of gas, that dictates the frequency of inspections.
Determining Your Leak Check Frequency
The required interval between mandatory leak checks is not a single, fixed period. It is a variable that depends on a specific set of factors related to your installation. The primary goal of these checks is to minimise the release of F-gases into the atmosphere, so the frequency is directly related to the potential risk your system poses [1][2].
Several key factors must be considered:
-
Total CO₂ Equivalent: This is the most important factor. The calculated tonnes of CO₂ equivalent for your system will place it into a specific category, which corresponds to a minimum inspection frequency. A higher CO₂ equivalent value generally leads to more frequent required checks.
-
Refrigerant Type: As discussed, the GWP of the refrigerant is a critical component of the CO₂ equivalent calculation. Consequently, systems containing gases with a higher GWP are more likely to require frequent checks.
-
Presence of a Leak Detection System: The regulations make a distinction for equipment that is fitted with a permanent, automatic leak detection system [1]. If your installation has a system that continuously monitors for refrigerant loss and alerts you to a leak, the required frequency of manual physical checks may be different. For such a system to be considered, it must be functional and subject to its own regular operational checks.
To determine your specific obligations, you must first complete the CO₂ equivalent calculation. Once you have this value, a qualified technician can advise on the corresponding check interval. It is imperative to adhere to this schedule to ensure compliance and maintain the environmental integrity of your system.
The Critical Role of Service Records
Maintaining a comprehensive and up to date service record, often referred to as a logbook, is not just good practice; it is a fundamental requirement of F-gas regulations [1][2]. This logbook serves as the official history of your refrigeration or air conditioning equipment and is the primary evidence that you are meeting your legal obligations.
A service record should be a detailed account of all interactions with the refrigerant circuit of the system. Each entry should be made by the certified technician performing the work and must include clear, precise information. A thorough logbook provides a running account that demonstrates what checks have taken place and when. This is essential for proving compliance during an audit by regulatory authorities.
Furthermore, these records are a practical tool for effective system management. For a technician, the logbook provides immediate access to the system’s history, which can be invaluable for diagnosing faults, understanding performance trends, or planning future maintenance. For the equipment owner, it provides a transparent overview of the system’s health and the costs associated with its upkeep. It also ensures a smooth handover of responsibilities if you change service providers or sell the property where the equipment is installed. Failure to maintain proper records can be considered a breach of regulations, so it is vital to ensure a logbook is created for each relevant system and is diligently updated after every service or inspection.
Sources: [1] EUR-Lex, Verordening (EU) 2024/573 https://eur-lex.europa.eu/eli/reg/2024/573/oj [2] IPLO, F-gassen https://iplo.nl/regelgeving/regels-voor-activiteiten/installaties/koelinstallatie/f-gassen/
Sources
- [1]EUR-Lex, Verordening (EU) 2024/573 · accessed 2 October 2026
- [2]IPLO, F-gassen · accessed 2 October 2026
This article is for information only and does not create any legal rights.
Related serviceMaintenance and service
Related articles
F-gases and regulations · 6 min read
F-gases: what rules apply to your system?
EU Regulation 2024/573 sets requirements for equipment containing fluorinated refrigerants.
Read article →F-gases and regulations · 5 min read
R410A or R32: what about your existing air conditioning?
The industry is moving towards lower-impact refrigerants. An existing system does not necessarily need immediate replacement.
Read article →Energy and grants · 7 min read
Energy label C for offices: where do you stand?
Many offices larger than 100 m² have needed at least energy label C since 1 January 2023.
Read article →